Treatment For Closed System

NT-200

NITRITE & BORAX BASED CORROSION & SCALE INHIBITOR FOR CLOSED RECIRCULATION SYSTEM

PRODUCT DATASHEET

Product Description

NT-200 is a clear liquid combination of nitrite, borate, and triazole corrosion inhibitor (containing no chromate or phosphate) designed to control pitting and galvanic action in closed recirculating hot and chilled water systems.

The non-chromate, non-phosphate, non-toxic nature of NT-200 makes it possible for plants to treat their hot and chilled water systems without the danger of creating pollution problems.

NT-200 is specifically designed for control of corrosion, pitting, and galvanic action in closed systems where dissimilar metals may be present.

Advantages

  • Compatible with alcohol- and glycol-based antifreezers.
  • Safe and easy to handle and use.
  • Controls corrosion of both ferrous and non-ferrous metals.
  • Protects the system from corrosion and pitting attacks.
  • Non-staining formulation.

Dosage

Normally, the treatment should be used in a sufficient quantity to maintain a sodium nitrite residual of 650-1200 ppm. After an initial dosage of NT-200 in the system, a maintenance dosage is generally performed due to weekly blowdown and water losses. Maintenance dosage will be calculated by a Maxon Representative by measuring water loss and water nitrite level.

Feeding

NT-200 is not used on a regular basis; hence feeding is one-time and mostly done manually. Maxon Representative will guide and demonstrate the feeding procedure and quantity best suited to the system in question.

Handling

Use all safety procedures before handling. Keep in a well-ventilated place. Do not store this material near food, feed, or drinking water. Do not store in metallic containers. Use only recommended materials for storage. Consult MSDS for other safety information.

Packaging

NT-200 comes in containers conforming to performance and mobility-oriented packaging specifications, in the following sizes:

  • 30 Kg PE container (on special request)
  • 210 Kg PE container
  • 1 metric ton IBC cage tanks

NT-200

MATERIAL SAFETY DATA SHEET
According to Regulation (EC) No 1907/2006, Annex II

Section 1: Identification & Company Undertaking

Chemical Name: NT-200
Product Code: UKAT-35
Chemical Composition: Polymeric Nitrite, Borax, Trizole, PAA, etc.
CAS Number: Not applicable to blend
Chemical Formula: Blend
Identified Usage: Corrosion & Scale Inhibitor (Closed loop chill & hot water system)

Supplier: Maxon Chemical Products (Pvt.) Ltd.,
121/A Gule Daman, College Road,
Lahore, Pakistan. 54000

Emergency Contact: Maxon Head Office (PK) – +92(42)35155441/2
Technical Principal: Maxon UK

Section 2: Hazards Identification

Hazard Overview:
May cause eye and skin irritation, respiratory and digestive tract irritation. Harmful if inhaled or swallowed.

Signs and Symptoms of Acute Overexposure:
Contact may cause irritation or burns to eyes, skin, respiratory tract, and mucous membranes. Harmful if swallowed. Harmful if inhaled.

Signs and Symptoms of Chronic Overexposure: NDA

Medical Conditions Generally Aggravated by Exposure: None Known

Section 3: First Aid Measures

Inhalation: Remove patient to fresh air.

Ingestion: Give victim 2-4 glasses of water or milk to dilute the product. Induce vomiting by tickling the back of the throat.

Skin Contact: Remove contaminated clothing and footwear. Wash and rinse skin with soap and water. Call poison control for treatment.

Eye Contact: Immediately flush eyes with water for 15 minutes. Get medical attention immediately.

Note to Physician: None

Section 4: Stability and Reactivity

Stability: Product is stable under normal conditions. May also be reactive in some circumstances.

Hazardous Decomposition Products: Gaseous nitrogen oxides

Incompatibility: Acids, ammonium compounds, reducing agents (usually cyanides, thiocyanates, certain combustibles, and organics)

Hazardous Polymerization: Will not occur

Conditions to Avoid: Incompatible chemicals

Section 5: Toxicological Information

RTECS:

  • CAS# 7732-18-5: ZC0110000
  • CAS# 7632-00-0: RA1225000
  • CAS# 1303-96-4: VZ2275000
  • CAS# 1310-58-3: TT2100000
  • CAS# 64665-57-2: 1003731ST
  • CAS# 9003-01-4: AT4680000

Carcinogenicity:

  • IARC: Poly(Acrylic acid) – Group 3 known animal carcinogen, but not listed by ACGIH, NIOSH, NTP, or OSHA.
  • Other ingredients are NOT found on any lists published by ACGIH, IARC, NIOSH, NTP, or OSHA.

Section 6: Accidental Release

Contain spill. Use absorbent to clean up. Recover for use if possible, or transfer to a clean, dry steel tank or lined fiber drum, close, and label the oxidizer. Dispose of at an approved waste disposal facility.

Scroll to Top